Search

RH5

RH5

RH5

  • Limit value switch for temperature, NTC thermistor

  • Simple application; for harsh environments

  • Limit value adjustable by drum scale

  • Normally open or normally closed version

  • Compact and robust construction

  • Operating status indication by integrated LED

Limit value switches of type RH5 monitor electrical measured variables. The integrated relay switches when the actual value present reaches the set target value. Furthermore, limit value switches of this type are equipped with sensor monitoring for short circuits and wire breaks. Its compact and robust design, as well as the relevant shipbuilding approvals, make this product ideal for marine applications.

Supply voltage UB

18...32 VDC

Input signal

NTC thermistor

Output contact

Volt-free change over switch contact, normally closed or normally open

Maximum switching capacity

30 W (1 A at 30 VDC; 0.5 A at 60 VDC); 40 W (0.2 A at 220 VAC)

Operating temperature

-20°C...+70°C

Connection

DIN46244 tab connector, gold-plated A6.3 x 0.8

Mounting

TS32 G-rail or TS35 top hat rail

Part code structure

RH5

1

-A

Example: RH51-A

Input range

Output signal

Part code RH5 …

Input range

1

40 … 120°C = 2663.3 … 194.65 Ω (NORIS temperature sensors TH.1)

2

5 … 70°C = 2181 … 231 Ω (NORIS temperature sensors TH.2)

Output contact

Output contact as changeover switch in normally closed

A

Output contact as changeover switch in normally open

RH5

__

-__

Example: RH51-A